Description

The MGate MB3170 and MB3270 are 1 and 2-port Modbus gateways, respectively, that convert between Modbus TCP, ASCII, and RTU communications protocols. The gateways provide both serial-to-Ethernet communication and serial (master) to serial (slave) communications. In addition, the gateways support simultaneously connecting serial and Ethernet masters with serial Modbus devices. The MGate MB3170 and MB3270 Series gateways can be accessed by up to 32 TCP master/clients or connect to up to 32 TCP slave/servers. Routing through the serial ports can be controlled by IP address, TCP port number, or ID mapping. A featured priority control function allows urgent commands to obtain an immediate response. All models are rugged, DIN-rail mountable, and offer optional built-in optical isolation for serial signals.
Integrate TCP Masters without Altering the Modbus RTU/ASCII Network or Software
The MB3270 can integrate Modbus TCP with Modbus RTU/ASCII, without modifying the existing Modbus RTU/ASCII architecture or software. With the serial redirector function, a serial master can maintain direct access to serial slave devices through a specially mapped serial port. This allows the serial and TCP masters to access serial slaves simultaneously.
Optical Fiber for Ethernet Communication
The MGate MB3170 Series includes 100BaseFX fiber models that support transmission distances up to 4 km for multi-mode models, and up to 40 km for single-mode models. Optical fiber is well-suited for industrial applications because it is immune to electromagnetic noise and interference. For environments that experience high ground loop voltages, fiber provides the best isolation protection, and because there is no danger of sparking, optical fiber is safer than copper wire to use in hazardous environments.
Auto-Device Routing for Easy Configuration (Patent Pending)
Moxa's Auto-Device Routing function helps eliminate many of the problems and inconveniences encountered by engineers who need to configure large numbers of Modbus devices. A single mouse click is all that's required to set up a slave ID routing table and configure Modbus gateways to automatically detect Modbus requests from a supervisory control and data acquisition (SCADA) system. By removing the need to manually create the slave ID routing table, the Auto-Device Routing function saves engineers significant time and cost.
Priority Control for Urgent Commands (Patented)
As Modbus networks increase in size and complexity, the lag time between commands and responses becomes a major concern. Advanced models of the MB3000 Series provide a priority control function for urgent commands, allowing users to force certain commands to get an immediate response. Depending on your system's requirements, different methods are available to define which commands receive priority.




Ethernet Interface
10/100BaseT(X) Ports (RJ45 connector)
2 (1 IP, Ethernet cascade) Auto MDI/MDI-X connection
Magnetic Isolation Protection
1.5 kV (built-in)
Ethernet Software Features
Industrial Protocols
Modbus TCP Client (Master), Modbus TCP Server (Slave)
Configuration Options
Web Console (HTTP/HTTPS), Device Search Utility (DSU), MGate Manager, MCC Tool, Telnet Console
Management
ARP, DHCP Client, DNS, HTTP, HTTPS, SMTP, SNMP Trap, SNMPv1/v2c/v3, TCP/IP, Telnet, UDP, NTP Client
MIB
RFC1213, RFC1317
Time Management
NTP Client
Security Functions
Authentication
Local database
Encryption
HTTPS, AES-128, AES-256, SHA-256
Security Protocols
SNMPv3
HTTPS (TLS 1.2)
Serial Interface
No. of Ports
MGate MB3170 Series: 1 MGate MB3270 Series: 2
Connector
MGate MB3170/MB3170I: DB9 male for RS-232 and terminal block for RS-422/485 MGate MB3270/MB3270I: 2 x DB9 male
Serial Standards
RS-232/422/485 (software selectable)
Baudrate
50 bps to 921.6 kbps
Data Bits
7, 8
Parity
None, Even, Odd, Space, Mark
Stop Bits
1, 2
Flow Control
DTR/DSR, RTS Toggle (RS-232 only), RTS/CTS
RS-485 Data Direction Control
ADDC® (automatic data direction control)
Pull High/Low Resistor for RS-485
1 kilo-ohm, 150 kilo-ohms
Terminator for RS-485
120 ohms
Isolation
2 kV (I models)
Serial Signals
RS-232
TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422
Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w
Data+, Data-, GND
RS-485-4w
Tx+, Tx-, Rx+, Rx-, GND
Physical Characteristics
Housing
Plastic
IP Rating
IP30
Dimensions (with ears)
29 x 89.2 x 124.5 mm (1.14 x 3.51 x 4.90 in)
Dimensions (without ears)
29 x 89.2 x 118.5 mm (1.14 x 3.51 x 4.67 in)
Weight
MGate MB3170 Series: 360 g (0.79 lb) MGate MB3270 Series: 380 g (0.84 lb)
Environmental Limits
Operating Temperature
Standard Models : 0 to 60°C (32 to 140°F) Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Storage Temperature (package included)
-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity
5 to 95% (non-condensing)


Manufacturer Part No:

MGate MB3270 V2.6.0
Brand:

MOXA

Product Type:

-
UPC

-
Product Family:

Protocol Gateways
Shipping Weight:

0.3 kg
PB Part No:

IPCMXAMB327001
Product Model:

MGate MB3270



Warranty:
60 months *
* Warranty period is as stated above unless the manufacturer has chosen to specify a longer period.
All warranties are return to base unless otherwise specified.